Multi-line 300 PPU 300 ver. 1.x.x.

Multi-line 300 PPU 300 ver. 1.x.x.

You have chosen to download our software.

Within a few seconds, you will receive an email containing a download link.

Having trouble using the software? Please contact support@deif.com. 

Best regards, 

DEIF A/S

The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software

1.0.26.3

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

Changes:

• Fixed issue where the controller crashed creating a backup.

1.0.26.2

24/12/2023

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

Changes:

• Updated CODESYS libraries.

1.0.26.1

11/12/2023

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

Corrections:

• Optimised CPU performance.
• Fixed issue where engine cooldown was not stopped when changed to switchboard control.

1.0.26.0

07/12/2023

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

New features:

• Added emergency stop alarm to the parameter list.
• Added "Three-phase UL1L2 & IL1" as a new wiring mode option in the AC configuration.

Corrections:

• Corrected an issue where it was possible to override an application output from Modbus.
• Corrected an issue where the controller performed an unwanted restart due to an uncommon issue in Modbus.
• Corrected an issue where reading the IO status on Modbus could cause an unwanted restart of the application software.
• Corrected an issue where digital outputs stayed high after removing the configuration.

1.0.21.1

29/03/2023

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

Corrections:

1 - Fixed issue where the voltage offset in reactive power load share did not react

1.0.21.0

21/10/2022

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

New feature:

1 - Added support for multiple applications with a parameter to select active application and custom plant name. (Not supported by PICUS yet.)
2 - Added possibility to adjust frequency offset for power load share regulating.

Corrections:

1 - Fixed bug where SC does not close, because sync. never finishes in emulation.
2 - Fixed issue where "Ramping to xx" was stuck in status text.
3 - Fixed issue where IO parameter configuration was passed on from one external breaker or a heavy consumer on the single line to another during commissioning. IO configuration and parameters are not reset.
4 - Fixed issue where engine ready delay was ignored before regulation.
5 - Fixed issue where manual regulation didn't work in emulation.
6 - Fixed issue where analogue regulation was unstable in emulation.
7 - Fixed issue with GAM3.2 not working in emulation.
8 - Actual power total in % is now showing on DU-300 (Live data) and in PICUS.

1.0.20.0

20/07/2022

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.20.0

Minimum required version of PICUS: 1.0.19.0

PPU 300

New feature:

  • Added Aftertreatment dashboard
  • Added possibility to create custom popups from CODESYS
  • Added possibility to set custom status text from CODESYS
  • Custom counters added to CODESYS and Customlogic
  • Added possibility to setup power transformer on genset and hybrid controllers

Changes:

  • Backup of eventlog changed to get latest 1000 events.
  • Corrected min, max and default value for AVR relay output Maximum ON time

Corrections:

  • ACM3.1 card will not start protections if settings is lost during operation. A power cycle of the controller will be required to restart the protections. Alarm ""ACM protection not running"" will be shown continuously if the problem occur.
  • Fix the issue there EDG only have 1 set of synchronization settings
  • Fixed - Reboot of controllers required after SW update
  • Fixed issue where AC protections could change "AC setup" after power cycle of the controller
  • Fixed issue where is not possible to stop SC or SG in emulation, if the breaker was closed
  • When synchronising using static sync. The GOV and AVR on the syncing controller should no longer give spikes when a blackout happens on busbar.

DU 300:

New features:

  • Introduces a new view for exhaust after-treatment dashboard increasing the support of Tier 4 and Stage V engines.

 

1.0.18.0

23/04/2022

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.18.0

Minimum required version of PICUS: 1.0.18.0

PPU 300

New feature:

  • Added custom alarms in CODESYS
  • Added possibility to disable display buttons in individual groups
  • Added control signal to engine communication + extra protocols
  • Reset horn is possible to reset with input

Corrections:

  • Action for the synchronization failure alarm is now visible in PICUS and DU.
  • Fixed issue where counters does not work in Custom Logic
  • Fixed issue where synchronize indicator on display is visible with dead busbars
  • Fixed issue with alarm test, does not work when alarm state was unacknowledged no alarm
  • Fixed problem where Picus would show empty Application or I/O status page.
  • Fixed issue where measurement averaging has causing a very small offset the the averaged measurement.
  • Fixed issue where emulated values was slower when using measurement averaging.
  • Fixed issue where the additional logged values in the event log could be incorrect when measurement average is used.

DU 300:

New features:

  • DU300 button management.
    • Added the ability to disable (and enable) the buttons of the DU300 by parameters.
    • The buttons are disabled in blocks related to their functionality.
    • This provides more possibilities to configure the controller to the application's requirements.

Corrections:

  • Fixed an issue with the differentiation of two synchroscopes with the same measurements, like an EDG.
  • Fixed an issue related to ANSI codes shown on the alarm popup.

1.0.17.0

10/02/2022

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.17.0

PPU 300

New Features:

  • For CODESYS application it is now possible to have a function block for special hardware, without having the hardware.

Corrections:

  • Changed the maximum value for Breaker close failure delay to 30 seconds.
  • Changed the maximum value for Breaker Pulse ON time to 60 seconds.

DU 300

Changes:

  • Improved navigation and look of the Parameters page.

Corrections:

  • Solved an issue that would cause the DU 300 to crash when downgrading DU software.

1.0.16.0

13/10/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.16.0

PPU 300

New Features:

  • Added ANSI code tag to relevant alarms
  • Added possibility for disabling Ethernet ports
  • Added REST version to version page
  • Change the behavior of "Update" input for custom parameters in CODESYS
  • Added any functionality to ICC flags
  • Increase number of ICC flags to 32

Corrections:

  • Fixed issue where GAM3.2 stand alone was active when regulator was set "OFF"
  • Fixed issue in CODESYS where custom parameters write FB not working after read FB has been called

DU 300

New Features:

  • Support for Tags:
    • New menu for options to display the tags set in parameters.
    • Options for tag visualisation include: Alarm pop-up, alarm list, logs page and parameter page.

Changes:

  • Update to languages
  • Connection improvements

Corrections:

  • Solves an issue where the display could enter a manual loop after returning from synchroscope.

1.0.15.0

12/07/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.1

PPU 300

New Features:

  • CPU load is now accessible and displayed through the performance widget.
  • Change of counters is added to the event log.
  • CPU load is now a measurement shown as a Live data value or a Modbus address, and it is accessible as an Analogue Output.
  • New counters relating to engine/inverter starts are added.
  • New counters relating to breaker operations are added.
  • Energy import and difference counters are added to hybrid.
  • External breaker states are added to CustomLogic.

Changes:

  • Counters are now specifically signed or un-signed.
  • Text on Live data screen is changed for Engine speed.
  • CustomLogic bit outputs are now reset to 0, and then deleted from the configuration.

Corrections:

  • Corrected that "Different power management rules activate" alarm was triggered incorrectly.
  • Corrected the behaviour of Continuous breaker.
  • Corrected missing paths for Modbus "Inhibited" flags.
  • Corrected an issue where the display would jump to sync. view if a trip alarm occurred.
  • Corrected an issue where "ball" on the synchronization view could change between red and green, when the breaker was closed.
  • Corrected an issue where the alarm counter did not increment if the state was not State A – Normal.
  • Corrected an issue where a Stand-alone EDG would not deload the GB in SEMI-AUTO mode.
  • Corrected an issue where the scale "(4 to 20mA) to (0 to 100%)" displayed 4.0mA instead of 0.0mA on GAM3.1.

DU 300

Changes:

  • Font size and duration of error message increased in the virtual keyboard.
  • New counters icon for alignment with PICUS.

Corrections:

  • "Missing" counters removed from the display.
  • Units shown for the I/O terminals.
  • Counters are now limited based on the counter type.
  • Display restarts on I/O pages when fieldbus configuration is updated.
  • LED's no longer light up before the screens become active.
  • Passwords with special characters can now be used from the display.

1.0.14.1

01/06/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.0

PPU 300

Corrections:

  • Allows IOM3.4 Firmware revision 1.0.0.2.

DU 300

New features:

  • Synchroscope view.

Changes:

  • Local display configurations (for example, brightness and units) will now be kept when new application software is installed.

Corrections:

  • Bar graphs and gauges animations performance is increased.
  • Fixed an issue in View Design where up/down keys lost focus after a blue pop-up.
  • Fixed an issue in Parameters where up/down buttons would not be shown.

1.0.14.0

21/05/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.0

PPU 300:

New feature:

  • Emulation feature is added.
  • It is now possible to open the breaker when there is a position failure.
  • All I/O cards and CAN bus values can now be mapped in Modbus.
  • ECU: Communication failure is added. When communication is expected, but not present, an alarm is triggered.
  • Live data: J1939 protocol is now available for engine communication.
  • An option for customers to add CODESYS application version to the version page is added.
  • Idle run start is added.
  • Idle run stop is added.
  • Inhibit for idle run is added.
  • It is possible to skip Idle Run Stop by requesting "Stop" again.
  • It is possible to skip Idle Run Start by requesting "Start" again.
  • CODESYS inputs and outputs are available in Modbus.
  • CustomLogic inputs and outputs (digital and analogue) are available in Modbus.
  • Inhibit status for alarms is available in Modbus.
  • Alarm property "Remove from service" is now available in Modbus.
  • The external regulation value can now be read in the regulator status tool.
  • State of the manual regulation input can now be read in the regulator status tool.
  • The source of regulation can now be read in regulator status tool.
  • Engine ECU: Process data alarms are added, and it is now possible to get application alarms from either the ECU or an analogue input.
  • Engine ECU data has been mapped to communication (incl. standard Modbus) and is configurable in flexible Modbus.
  • New ECU: Auto discover is added and can be activated from either CustomLogic, CODESYS, Modbus, or Commands.
  • Live data groupings are arranged in groups according to the engine sub systems.
  • Live data screen view: Now you can see measurements from different sources based on the priority Analogue/IO over ECU.

Changes:

  • The Modbus connections for Idle Time Expired are changed from 100 seconds to 10 seconds.
  • The default AC setup values are changed.
  • "AVR trip" location in CustomLogic for Hybrid is cleaned up.
  • The text for Hybrid is corrected.
  • Spelling error: "Deloading" is changed to "De-loading".
  • Phase sequence error text is corrected for Hybrid.
  • Default settings for blackout detection mismatch alarm are changed.

Correction:

  • Fixed that Modbus crashed when trying to connect many times, and not getting a new connection.
  • Fixed an issue with continuous breaker with mismatch between closing failure and output states.
  • Breaker operation counter increment is now working.
  • Load sharing miscalculation for SG is corrected.
  • Trip counter is now incremented for Hybrid when a trip occurs.
  • Shore and shaft supervision status is fixed.
  • Fixed an issue where default max value for EIM3.1 resistance analogue input sensor was to high.

DU 300

New features:

  • Synchroscope view.

Changes:

  • Local display configurations (for example, brightness and units) will now be kept when new application software is installed.

Corrections:

  • Bar graphs and gauges animations performance is increased.
  • Fixed an issue in View Design where up/down keys lost focus after a blue pop-up.
  • Fixed an issue in Parameters where up/down buttons would not be shown.

1.0.13.2

14/04/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.0

PPU 300:

Correction:

  • Fixed issue where controller restarts if writing to oil pressure on Modbus
  • Included bugfix on EIM3.1

DU 300

New features:

  • Synchroscope view.

Changes:

  • Local display configurations (for example, brightness and units) will now be kept when new application software is installed.

Corrections:

  • Bar graphs and gauges animations performance is increased.
  • Fixed an issue in View Design where up/down keys lost focus after a blue pop-up.
  • Fixed an issue in Parameters where up/down buttons would not be shown.

1.0.13.1

24/02/2021

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.15.0

PPU 300:

Corrections:

  • Fixed an issue where the link status of a CODESYS digital output was not correct after download/restore.

DU 300:

New features:

  • Synchroscope view.

Changes:

  • Local display configurations (for example, brightness and units) will now be kept when new application software is installed.

Corrections:

  • Bar graphs and gauges animations performance is increased.
  • Fixed an issue in View Design where up/down keys lost focus after a blue pop-up.
  • Fixed an issue in Parameters where up/down buttons would not be shown.

1.0.13.0

16/02/2021

Versioning changed for alignment within platform.

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.14.0

PPU 300:

New features:

  • AC measurement averaging:
    • It is now possible to use averaging filters (200ms and 800ms) to reduce the value fluctuations from the high performance of the measurement cards.
    • The averaging filter can be applied selectively to different types of measurements.
    • AC measurement averaging affects data displayed by DU 300, PICUS, trending, CustomLogic, CODESYS, and Modbus.
    • AC measurement averaging does not affect protections and regulation values.
  • EIM3.1 Safety shutdown function:
    • EIM3.1 can now be used as a safety shutdown module.
    • EIM 3.1 will be able to run the engine in stand-alone mode should it no longer be able to communicate with the main processor card (PCM).
  • Hybrid controller type added.
  • Support of electronic engines protocols (EIC):
  • Supports the Generic J1939 protocol for reading.
  • J1939 values, alarms and historical events are now available.
  • New engine measurement inputs + alarms added for: Oil pressure, Oil temperature, Coolant temperature, and Coolant level.
  • Flexible application drawing:
    • It is now possible to customise the application drawings to provide a customisable interface.
    • The design of applications with multiple ring connections is now supported.
  • CODESYS version information:
    • It is now possible to readout CODESYS versions in PICUS in the information tab.
    • It is now possible to readout if the licence key is active or not.
    • It is now possible to readout what type of license is active.
  • CustomLogic IO added to Flexible Modbus

Changes:

  • Update rate of live data in display and PICUS is increased.
  • Changed: Possible to change time and date individually from PICUS.
  • The password length can now be 1 to 32 characters.
  • New default password is "0" for all users.
  • Controller type can now be changed during backup restoration.
  • Changed parameter menu structure for Cos Phi set point. Set point, offset and limit.
  • When changing single-line diagram - cleaning up alarms related to redundant breaker.


Corrections:

  • Issue fixed where breaker opened before breaker open point is reached.
  • Fixed issue where hidden Modbus addresses was accessible.
  • Fixed issue where NELs trip if breaker is opened.
  • Fixed issue with rounding problems on decimal values on Modbus data.
  • Fixed issue where changing of counters from Modbus not was saved if there was a controller power cycle shortly after.
  • Fixed issue where remote and local LEDs both were turned on.
  • Fixed issue with unsupported functions in CODESYS libraries.
  • Fixed issue where trip output does not activate when "breaker position failure" is active.
  • Fixed issues where custom parameters in CODESYS stop working after multiple downloads of CODESYS application.
  • Fixed rare issue where backup file was corrupted.
  • Fixed issue where custom alarms do not get units in the alarm and event logs.
  • Fixed issue where GAM3.2 stand-alone mode does not work with PWM output.
  • Fixed issue where regulator did not reset on external stop.
  • Fixed issue where extended stop delay was skipped on external stop.
  • Alarm timer expired flag data added to Modbus.
  • Fixed issue where BTB was not deloaded by DG.
  • Fixed issue where different controller software will run in same system.
  • Fixed issue where breaker open signal could be sent because of missing inhibit info on ACM3.2.
  • Fixed issue where AMC3.2 protections did not work on the Shaft generator.

DU 300:

New features:

  • Custom alarm action suppression: It is now possible to enable alarm suppression for custom alarms from the display.
  • Fast data interface: Faster update rate of gauges, counters, status texts, and live data views.
  • Engine communication:
    • J1939 alarms and historical events.
    • Fieldbus, configuration, supervision and CANbus error handling.

Corrections:

  • Fixed translation of texts in the View designer.
  • Fixed translation of message box popup breadcrumb.
  • Fixed DU300 live data subheader text cutting lower case p, g, j, q, y letters.
  • Fixed DU300 showing negative ampere.
  • Fixed conversion between C and F not having effect on scaling (View design).

1.0.7.0

09/06/2020

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.11.0

PPU 300:

New features:

  • Support for the new IOM3.2 and IOM3.3 cards.
  • Derate of nominal power is now possible with an analogue input.

Correction:

  • Fixed an issue where PICUS supervision would update if the regulator type was changed.
  • Fixed an issue where EIM3.1 relay 4 wire breaker supervision was not working.
  • Fixed an issue where IOM3.4 custom texts could be mixed up if more than one card were used. This fix result in a break of backward compatibility, if custom text has been used on IOM3.4 cards.
  • Fixed an issue where adding a previously used extension rack to a new system could cause the controller to restart.
  • Fixed an issue where connection to an extension unit could cause the controller to restart in a system with more than two extension units.

DU 300:

New features:

  • Support of IOM3.2 and IOM3.3.

1.0.5.0

17/12/2019

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.11.0

PPU 300

New features:

  • Fixed that the display couldn't show negative values on graphs.
  • Live data screens can now be configured by the user.
  • Enhanced Backup/Restore: Restoring of CODESYS is now optional.
  • Fixed that the alarm "Different single-line diagram" would trigger during broadcast of a single-line.
  • Continous breaker: Configuration requiring only one output is now possible.
  • "Fast overcurrent" now has configurable max. range.
  • Breaker feedback: Configuration requiring only one input for feedback is now possible.
  • Support for Network Time Protocol (NTP).
  • Command sources: Setting of permissions for each individual Local/Remote source (PICUS, Display, Modbus, I/O or CustomLogic) is now possible.
  • Alarms can now be tested individually.
  • Support for ACM3.2 card.
  • Modbus: Registers for alarm trip value is now available.
  • Alarm "Inverse time overcurrent": Threshold is now configurable.
  • Redundant breaker feedback is now possible.
  • Spring loaded breaker: Arming of spring is now possible via input.
  • Breaker tripping and opening can now be assigned to individual outputs.
  • AVR can now be tripped by specific alarm actions.
  • Single line: Support for 32 controllers.
  • Flexible Modbus: User configuration of register mapping and support for additional servers.
  • Alarm details now include number of times the alarm was triggered.
  • Nominal settings: 4 sets are now available.
  • User interfaces: Different languages are now supported.
  • Modbus: Registers for Date/Time are now available.
  • Configurable alive/watchdog functionallity is now available.
  • IO Extension units: This feature allows expansion of a ML 300 system with additional decentralized racks containing the desired I/O cards.
  • Firmware update: Replacement cards can be updated without using the utility software
  • Firmware upgrade: In case of controller not beeing ready for update, detailed information about cause is now shown.
  • CODESYS: Improved I/O response time.

Changes:

  • Fixed that name of parameter group "Power supply" in relation to "EIM" was misleading. Moved to the "Hardware" section.
  • Fixed that naming of GAM3.2 I/O's did not comply with naming of other I/O's.
  • Fixed that GOV and AVR parameters did not use the same layout.
  • Minimum OK frequency minimum value and Minimum OK voltage changed to 70 %.
  • Not possible to set inhibits on "System not OK" alarm.

Corrections:

  • Fixed that software version check was only made on the first card in a rack.
  • Fixed that configurable I/O's could maintain their state after beeing unconfigured.
  • Fixed that alarm actions not allowed for a given controller type could be selected anyway.
  • Fixed that event "Start enabled deactivated" could register, even if conditions were not met.
  • Fixed that alarms for "Power import" were missing on BTB.
  • Fixed that changing the calculation method for "Q nominal" would not reflect on the HMI custom view.
  • Fixed general error in sync check.
  • Fixed that some labels in the PICUS menu hierarchy would be truncated.
  • Fixed that BTB blackout close would display the wrong pop-up text ("Busbar A voltage/frequency not OK").
  • Fixed that removing input function from an Analogue output did not reset the Analogue output to "0".
  • Fixed that Active/Reactive power differential counter pulse functionallity did not activate when importing power, only when exporting.
  • Fixed that "Running hour counters" were missing in CustomLogic.
  • Fixed that inhibit "ACM wirebreak" did not reflect the correct state.
  • Fixed that in an engine stop sequence during "Crank off time", if a "Stop command" was issued and the engine had already stopped, the "Crank off timer" was not aborted.
  • Fixed that alarms for P and Q load sharing failure were active during load share ramp-up.
  • Fixed that regulation delay for GOV and AVR was ignored during engine start.
  • Fixed that GOV and AVR regulation would continue during engine stop sequence.
  • Fixed that "Power derate" would wrongly also affect "Breaker open point".
  • Fixed that the alarm "Close failure" on a "Compact breaker" would trigger prematurely.
  • Fixed that some engine states were not available in CustomLogic.
  • Fixed that regulation delay for GOV and AVR was ignored during engine start.
  • Fixed that alarms for "Phase sequence error" were reversed with regards to A/B side.
  • Fixed that requesting "Reset to offset" on GOV or AVR regulator would result in output values not matching the setting in parameters "GOV/AVR output offset".
  • Fixed that the triggered value in alarm details would not be updated if an alarm was re-triggered.
  • Fixed non-responsive Modbus commands related to breaker operations.
  • Fixed the default parameter values for Ti, GOV and AVR manual regulator.
  • Fixed that AVR regulator mode "Fixed Voltage" did not "freeze" the regulator output, when the system lost one or more of the AC measurements.
  • Fixed that alarms with fail class "Block" would not abort the synchronize sequence.
  • Fixed that "SI-unit" label was repeated on some parameters settings.
  • Fixed that digital inputs were unavailable in CustomLogic.
  • Fixed that on the Supervision screen in PICUS the actual state of the busbar and the color representing it would mismatch.
  • Fixed that the alarm "Redundancy broken" had wrong trigger conditions.
  • Fixed that the alarm "Protection set point out of range" had wrong trigger conditions.
  • Fixed that "GAM3.2 status OK" was available as I/O source in PICUS, even when GAM3.2 was not part of the controller configuration.
  • Fixed that the pop-up message "Breaker close cancelled" did not show when conditions were in fact met.
  • Fixed that "Power derate curve" was limited to a max. setting of 200. Increased to 1000.
  • Fixed that "Derate" functionallity did not use the same base for "Power Available" calculation in [%] and in [kW], thus resulting in conflicting values.
  • Fixed that if a blackout is detected (real or loss of measurements) during the synchronisation part of a close sequence the sequence would be cancelled.
  • Fixed that supervision of SCs in PICUS would show shore measurements where ship measurements were supposed to be shown.
  • Fixed that the Backup and Restore action buttons after a restore were no longer shown in the PICUS menu.
  • Fixed that the alarm "Inverse time over-current" were not available for use on "Outputs".
  • Fixed that alarm "Busbar Phase sequence error" was unavailable in CustomLogic and Outputs.
  • Fixed that certain Modbus addresses could not be used as commands.
  • Fixed that "Operations counter" did not work for external breakers.
  • Fixed that "Acknowledge alarms" in combination with the "Alarm TEST" functionallity could result in a controller restart.
  • Fixed that CustomLogic ICC flags could become unavailable.
  • Fixed that alarms related to Generator protections would remain triggered if "Delay" was set to 0.0 seconds.
  • Fixed false detection of "Engine running" due to "noisy" busbar.
  • CODESYS: Fixed that some features in libraries and on Modbus, related to alarms, were missing.
  • Fixed that "Engine ready delay" would be ignored on SGs.
  • Fixed that on the display the "Counters" screen would show irrelevant entries.
  • Fixed that alarm and status for "Voltage or frequency not OK" did not trigger/update according to the settings.
  • Fixed that status for "Voltage and frequency OK" did not respect the parameter "Delay" settings.
  • Fixed that status text "Regulator frozen" could be shown when engine was in "stopped" state.
  • Fixed that Regulator ramp up/down did not work when operating in load share mode.
  • Fixed that alarm "Earth inverse time over-current" did not trip according to the settings.
  • Fixed that the alarm "CODESYS configuration conflict" would trigger repeatedly when downloading the CODESYS application.
  • Fixed inconsistent operation of the Regulator ramp functionality.
  • Fixed that CustomLogic could stop working if the controller was power cycled immediately after "write" of a new CustomLogic configuration.
  • Fixed falsely detection of Volt/Hz due to missing data from the ACM card.
  • Fixed that inhibit functionallity was not available for NEL groups.
  • Fixed that the Regulator status screen could show wrong values.
  • Fixed that error in CustomLogic menu configuration could result in a system error (Debug.lock).
  • Fixed a potential issue with inhibits not beeing updated.
  • Fixed that "Engine start-and-close" in combination with "Blackout close" would close the breaker before the engine was running.
  • Fixed that, in "I/O Configuration", inputs of type "DI" would show as "Undefined" when used for CustomLogic.
  • Fixed that "Derate" functionallity did not influence "Power Available" calculation correctly, thus affecting load share.
  • Fixed "Status OK" handling on ACM3.2.

DU 300

New features:

  • Extended alarm information.
  • Support of ACM3.2 V.1.0.0.0.
  • Support of Trip breaker outputs.
  • Support of /IO extension unit.

Changes:

  • Version page layout.
  • Backup and restore information.

Corrections:

  • Text bug in live views.
  • DU shows random info message.
  • Display showing wrong version number.
  • ApplState not updating text.
  • Backup from the display shows undefined text in information window.
  • Missing text for View design.
  • Restore info page: Not all cards is shown.
  • Display does not update alarm and event texts, when the custom text is changed on external breaker.
  • Backup status should handle error status.
  • Possible to enter alarm sub-menus with an empty alarms list.
  • Parameter settings are shown on the display, when setting up digital outputs.

1.0.4.1

04/03/2019

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.10.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

New features:

  • Support for multiple menu levels.
  • Display shows a pop-up window for the user before going into service mode.
  • Informs the user about development of the software.

Changes:

  • Support for PlantSupervision ver 1.0.5.0.

Corrections:

  • IOM3.4: DO's are not shown on display and in PICUS.
  • Display is not loading min. and max. from parameters when they are changed.
  • Power derate temperature is not shown on DU until power cycle.
  • When changing type, DU sometimes freezes until it restarts.
  • DU300 reboot in view designer.
  • Not able to close alarm pop-up.
  • Alarm "trigger value" is not updated if the alarm is already in the alarm list.
  • DU300 does not check versions for individual REST resources.
  • View designer cannot add counters to counters template.

1.0.4.1

19/11/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

  • No changes

1.0.4.0

06/07/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

New features:

  • Now possible to use 16 controllers in single line

DU 300

  • No changes

1.0.3.0

20/04/2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300 

New features:

  • CODESYS add-on
  • Frequency-dependent droop regulation
  • Support of GAM3.2 module with stand-alone possible
  • Able to abort "Lamp test" dialogue box
  • Power ramp configuration improved for better user experience
  • Selectable offsets for fixed P, Q and CosPhi regulation
  • Alarms made available in custom logic
  • Analogue I/O made available in custom logic
  • Parameter values made available in custom logic
  • Use external analogue signal as regulator set point
  • Alarm for F/V not OK made independent of GOV/AVR configuration
  • Power regulator set point range extended to -100 % to +100 %
  • GOV/AVR status display on PICUS and display
  • Regulation on SG 
  • Freeze regulation
  • Support of IOM3.4
  • Analogue value compare and operate function in custom logic

Changes: 

  • Optimised menu layout for better user experience
  • Improved ACM firmware update sequence

Corrections:

  • Compact breaker, optimised spring load sequence
  • "Blackout detection mismatch" functionality corrected
  • Fixed missing trip alarms
  • Manual regulation not possible with certain regulator settings
  • Fixed that "GB open-and-stop command" was ignored
  • Fixed that running detection by means of digital input could be delayed (affecting "Engine ready LED")
  • Fixed that in manual regulation mode, relay output could sometimes be left in "activated" state
  • Fixed that "Remove start" input could cause unintended short activation of crank relay
  • Fixed that cancelling a stop sequence could result in engine stopping anyway
  • Fixed that command "Open generator breaker and stop engine" could leave engine running
  • Fixed that running detection would not terminate crank timer
  • Fixed that alarms "GOV and AVR regulation error" would not be triggered
  • Alarms are always shown, even if configured as "suppressed"
  • Active start block alarm can no longer abort cooldown sequence
  • Genset temperature power derate functionality improved
  • "Start engine and close GB" command is now blocked by "Block engine start" command
  • Alarm on controller with breaker feedback error could result in breaker opening and engine stopping
  • DG suddenly becoming last controller on busbar during de-load, would trip its breaker
  • Detection of "Vector mismatch" improved
  • Fixed that "Freeze regulation" could leave relay output in "activated" state
  • Fixed that "BTB trip" command did not cancel synchronisation
  • Engine state in switchboard will now resolve to "Ready" instead of "Not Ready"

DU 300

New features:

  • Livedata configurator (View design)
  • Regulator screen (GOV/AVR)
  • Livedata dynamic reload integration
  • Message box popup

Changes:

  • Added display specific support for introspecting memory data
  • Update ID and labels on pair screen when entering the screen
  • Custom curves max precision changed from 2 to 8
  • Support for REST 1.0.4.0
  • Improvement to log output
  • Added direction to command list

Corrections:

  • DU relay not working
  • ML300 Backwards compatibility issues of DU
  • Parameter graph, special case fail
  • Livedata scales are not appearing
  • Event log was not telling which "command" (button) was pressed.
  • Blocking pop-up on DU 300 if controller software does not match.
  • Counter pop-ups now working correctly.
  • Display alarm list deadlock removed.
  • DU 300 able to change from service mode to app mode.
  • Inhibit counter on the parameters was showing wrong number of inhibits
  • Comma insted of dot between the (rack#,slot#) presentation of card name
  • Identify did not work when logged on
  • Corrections to dynamic reload of livedata
  • Corrections to eventlog navigation
  • Update value list on changes
  • Applying broadcast storm filter on startup
  • Display not showing Priority
  • Pair controller not working correctly with rework.

 

1.0.2.0

29/09/2017

New features:

  • Acces to all alarm status information from CODESYS
  • Extended status information for alarm functionblocks in CODESYS   

Changes: 

  • Software mismatch on hardware module(s) alarm only occur if first, second or third digit on IO card version is changed
  • New EIM 3.1 software 2.0.1.0

1.0.1.0

25/08/2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.6.0


PPU 300 

New features:
   1  - 4 directional over-current alarms have been added to BTB (ANSI 67).
   2  - 2 directional over-current alarms have been added to SC and SG (ANSI 67).
   3  - Support of lamp test function.
   4  - Support of controller identify function.
   5  - Active regulator mode will be deactivated if a new is requested.
   6  - Additional information regarding alarms, breaker-, busbar- and generator status made available on Modbus.
   7  - Added "Critical process error"" alarm.
   8  - Last DG will trip if no other feeders are closed in the plant.

Changes:
   1  - "Power supply" parameter menu renamed to "Hardware".
   2  - "Network" parameter group moved to "Hardware" instead of "Utility". 
   3  - "Reset ratio" renamed to "Hysteresis" for protection alarms.
   4  - General check that "Nominal settings" cannot be configured to 0.
   5  - "Fixed power factor" renamed to "Fixed CosPhi".
   6  - "Analog" renamed to "Analogue".
   7  - "System not OK" alarm action is changed to "Warning".
   8  - New ACM 3.1 software 4.0.1.4.
   9  - New PCM 3.1 software 2.0.0.2.
   10 - The others are version 1.0.3.0.
   11 - "Directional over-current" alarm min. and max. set points have been extended to -300 % and 300 %.
   12 - Only one regulator request is accepted if more have been received.
   13 - It is possible to configure action on "System not OK" alarm.

Corrections:
   1 - Controller types SC, SG and BTB stop synchronising if measure feedback disappears.
   2 – Regulator could freeze if regulators were used in custom logic.
   3 - Regulator continued to regulate after feedback failure on GB.


DU 300

New features:
- Implemented first part of custom stylesheets
- Curves have been added to parameters
- Lamp test
- Identify feature to communication screen
- Units change on display
                      
Changes:
- Navigation and editing in I/O input text is now possible from the keyboard
- Default live data views updated
- Edit line design has been updated
- Updated counter screen to use states
- Default text in keyboard will show resolution
- Live data screens dynamic update (step 1)
- REST version control improvement step 1 (A+B match)
- REST version control improvement step 2 (new REST resource implementation)
- Live data dial meter and vertical bar widgets improved
- Production screen changed to versions screen, production data now visible in about screen
- Added DNS possibility to communication screen
- Added IPv6 address to communication screen
- Live data using REST to build screen and widgets
- Terminal values updated to only show allowed precision
- Updated help screens
                      
Corrections:
- Custom inhibit does no longer clear other inhibit flags
- Placeholder text from previous screen does no longer influence logon screen
- Handling of empty list in pair screen
- Pair screen automatically keeps rescanning for controllers if previously connected to a controller
- Elements in parameters are represented in the same order as in the base unit
- Preparation of lists in the application improved
- Removed dot key from keyboard when value is integer, or precision is zero
- Network off pop-up did not show the first time the display lost connection
- Do not allow user to press OK in empty pair list
- Cardlist serial to be a string instead of integer
- Display reboots after setting up AVR
- No longer showing all functions when function groups is empty
- Cleaned up warnings
- Not able to enable/disable the alarm "Ethernet redundancy broken"

1.0.0.3

12/04/2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.5.0

 

PPU 300

Corrections:
   1- Trip and stop action did not stop the engine in switchboard mode 
   2- Customlogic inputs was evaluated wrong in scan
   3- Sync. type was changed back from Static to dynamic after a power cycle

DU 300

No changes

1.0.0.2

14/03/2017

Corrections:

  • Start and close command now works correctly if “Voltage and frequency OK” timer has been increased.
  • Open and stop command can also stop the engine if breaker is opened, when command has been sent.

1.0.0.0

21/12/2016

PPU 300: Initial release

DU 300 ver. 1.0.5.0:

New features:

  • Added placeholder text when the label is completly empty, when you enter an I/O name, the current name of the IO will be shown.
  • Support of 4 line pop-up in the display.
  • Displays the variant on the info/about screen.
  • New pair feature (select base unit).

Changes:

  • DU registration of 4 new languages.
  • DU REST 1.0.2.0 support.
  • Update DU help files.
  • Added REST version to "About screen" in row 3.
  • Made it possible to take pictures of the first pair screen

Corrections:

  • Changed home screen Alarm 8000002 to Alarms 800025 to match the path.
  • Removed two arrows that were shown in parameter groups that was not supposed to be there.
  • Display could have problems, connecting to base units if it was connected in a daisy chain.
  • Making the algorithm responsible for showing/hiding pop-up windows.
  • Updating status text, and diodes in DU is made faster.
  • Crash in start-up sequence removed.
  • Corrected some filtering of allowed functions.
  • Remove illegal references to parameters.
  • Incorrect text shown when valueList had less than 2 elements removed.
  • If alarm screen is detected in the screen history, the current screen is rewound to that alarm screen.
  • DU updating speed improved.
  • Pop-up header characters clip adjusted.
  • IO scale: impossible to select a custom scale with only 1 point.
  • Header text initialised.
  • Pairing pop-up cuts of text on very long labels.
  • Controller for selecting base unit.
  • Appending empty unit to analogue output functions not possible.
  • DU start-up screen has been corrected.
  • Label corrected to "Restart" display instead of "Reset".

Como sempre, recomendamos a instalação dos aprimoramentos oferecidos para que você possa desfrutar totalmente do seu produto DEIF.

Todos os softwares aprimorados podem ser baixados, à sua conveniência e de maneira gratuita pelo site www.deif.com sob a opção “Software” e, em seguida, “Software Download”.

Em caso de dúvidas ou se enfrentar problemas para encontrar o software relevante para o seu produto, fique à vontade para contatar a DEIF A/S pelo telefone + 45 96149614 ou no escritório local da DEIF. Como alternativa, você pode enviar um e-mail para support@deif.com. Estamos sempre prontos para ajudar!