Multi-line 2 GCU 100 Application Software series 1.xx.

You’re about to download Multi-line 2 GCU 100 Application Software series 1.xx.

The software you are trying to download is obsolete. Please download the latest version from this page.

You have chosen to download our software.

Within a few seconds, you will receive an email containing a download link.

Having trouble using the software? Please contact support@deif.com. 

Best regards, 

DEIF A/S

The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software

This software applies to the following DEIF products:

You’re about to download 1.02.1

The main changes implemented since the last version are as follows:

Changes:

  • When M-Logic cooldown threshold is selected, it will be used regardless if parameter 6214 is 0.
  • Improved RPM measurement.

Corrections:

  • EIC alarms used as low alarms would appear when the CAN communication was lost.
  • Idle run could cause external start not to work.
  • Running hour counter offset could be adjusted to more than 99999 hrs.
  • Engine could end up in an infinite state between crank and running detection.
  • Alarms added to prevent this:
    - Running detection reached timer (parameter 6351)
    - External engine stop detection (parameter 6352)
Ver. Date Description

1.02.1

15/03/2016

Changes:

  • When M-Logic cooldown threshold is selected, it will be used regardless if parameter 6214 is 0.
  • Improved RPM measurement.

Corrections:

  • EIC alarms used as low alarms would appear when the CAN communication was lost.
  • Idle run could cause external start not to work.
  • Running hour counter offset could be adjusted to more than 99999 hrs.
  • Engine could end up in an infinite state between crank and running detection.
  • Alarms added to prevent this:
    - Running detection reached timer (parameter 6351)
    - External engine stop detection (parameter 6352)

1.02.0

03/02/2016

New features:

  • Contrast offset added in parameter 9152.
  • PT 1000 sensors introduced in multi-input 6 and multi-input 7.
  • Several events and limits added to M-Logic.
  • Added one additional battery low alarm (parameter 4950).
  • Inhibits can be set in battery low/high menu (parameter 4950/4960/4970).
  • Oil renewal feature introduced.
  • Battery voltage column now available in every entry in the log information in the DEIF Utility Software.
  • Added three freely translatable texts in the view lines.
  • Added support of ADEC CAN open, shutdown override.
  • Added EIC manual speed regulation

 

Changes:

  • Multi-inputs made linear in application emulation.
  • Parameter ranges in parameters 1150 and 1160 extended.
  • Increased parameter 2112 maximum value.
  • Extended maximum limit in start on time, parameter 6183.
  • Hz/V Ok parameter 6821 minimum value now extended to zero.
  • Extended fuel fill check timer (parameter 6553).
  • Made it possible to enable/disable fuel fill check (parameter 6553).
  • Made it possible to use auto acknowledge on Ext. Comm. Error parameter.
  • Start attempt maximum limits changed. Extended stop timer minimum limit changed.
  • Language translation changed. From now on it is not possible to select a different font.  The two fonts are now merged together, and containing all previously used characters. New characters are added. If any unsupported signs are written to the device the signs  will appear as ' ' (space).
  • Three RMI sensor curves added. One for each RMI type.  It will be possible to choose them in channel 10460, 10630 and 10800 by selecting "Sensor type 4" in the DEIF Multi-line 2 Utility Software v.3.
  • Scaling range 1 kV - 75 kV changed to 0.4 kV - 75 kV.

Corrections:

  • Stop coil did not activate when start sequence was aborted.
  • Inhibit evaluation added to a number of AC alarms.
  • Missing digit to running hours corrected.
  • Sign of display values between -1.0...0.0 with one or two decimals shown correctly.
  • Missing EIC values in analogue delta alarms added.
  • Measurement through the MPU input caused periodical peaks in the RPM measurement, which could cause an unwanted trip of the generator breaker.
  • Change of AC scale caused several energy counter views to be displayed with wrong decimal point and unit.
  • M-Logic line combination misinterpretation corrected.
  • Application emulation couldn't start properly with breaker and engine commands selected as inactive.
  • The lower inhibit level for phase sequence error increased from 30 % to 70 % of nominal voltage.
  • PT sensor offset parameters now corrected to compensate for the cable resistance.
  • Unit and MTU ADEC(SAM) communication not started during certain power supply situations - corrected. (Updated correction to avoid start request after communication has been reestablished).
  • M-Logic command "Start and Close GB" was ignored during cool down.
  • SCANIA EMS2 correction of start/stop.
  • Clock synchronise over Modbus was causing the service timer to offset its current timer value - corrected.
  • Configuration of output relays corrected, so all functions can be connected to all available relays.
  • Selection of multi-inputs for fuel pump logic corrected.
  • Fuel pump relay could activate at power-up of the controller before fuel level measurement has settled.
  • Several Modbus (option H2) addresses were not working - corrected.
  • MTU MDEC 302/303 protocols battery voltage measurement corrected.
  • Idle run timer now resets at each start attempt.
  • View lines: Run absolute and energy total corrected.
  • Unit could reboot if a Modbus command was sent while 'Inhibit modbus commands' was active.
  • Running hour counter could reset unintendedly - corrected.
  • Running hour counter could reset unintendedly at power cycle - corrected.
  • Scania EMS2 KWP2000 log clear now possible.
  • Exhaust gas temperature - right/left was not shown correctly in display.
  • Storage of service timer values during reset corrected.
  • Relays could activate under boot sequence - corrected.

1.01.0

23/02/2015

New features:

  • Common alarm
  • Siren

Changes:

  • Relay 3 default setting changed from Horn to Not used

Corrections:

  • The functionality of not showing alarm in case of combination of the alarms used  in relays has been corrected
  • Idle run activation through digital input and reactivation after stop button functions have been corrected
  • Idle run function corrected

1.00.2

01/09/2014

Corrections:

  • Relay channel error after power up corrected
  • Missing menu for blackout control added
  • Phase-phase / phase-neutral selection for protections corrected
  • Parameter 3410 password corrected
  • MTU Smart Connect engine protocol updated
  • Forcing GB feedbacks in emulation corrected
  • Reactive power for L1L3L2 AC configurations corrected
  • Parameter 1201 + 1202 only available for 3-phase AC configurations 

1.00.1

26/11/2013

Corrections:

  • Day of week is not adjusted when the date is changed - Corrected
  • Several menu texts were not using translations - Corrected
  • ECU 100 (GCU 111 & 112): Not able to start on D.I Remote Start - Corrected

1.00.0

01/05/2013

  • First release

Como sempre, recomendamos a instalação dos aprimoramentos oferecidos para que você possa desfrutar totalmente do seu produto DEIF.

Todos os softwares aprimorados podem ser baixados, à sua conveniência e de maneira gratuita pelo site www.deif.com sob a opção “Software” e, em seguida, “Software Download”.

Em caso de dúvidas ou se enfrentar problemas para encontrar o software relevante para o seu produto, fique à vontade para contatar a DEIF A/S pelo telefone + 45 96149614 ou no escritório local da DEIF. Como alternativa, você pode enviar um e-mail para support@deif.com. Estamos sempre prontos para ajudar!